| Model: | SURT3000XLI |
| Output Power Capacity: | 2100 Watts / 3000 VA |
| Max Configurable Power: | 2100 Watts / 3000 VA |
| Nominal Output Voltage: | 230V |
| Output Voltage Note: | Configurable for 220 : 230 or 240 nominal output voltage |
| Efficiency at Full Load: | 91.00% |
| Output Voltage Distortion: | Less than 3% |
| Output Frequency (sync to mains): | 50/60 Hz +/- 3 Hz user adjustable +/- 0.1 |
| Crest Factor: | 3 : 1 |
| Waveform Type: | Sine wave |
| Output Connections: | - (8) IEC 320 C13
- (2) IEC 320 C19
- (3) IEC Jumpers
|
| Bypass: | Internal Bypass (Automatic and Manual) |
| Nominal Input Voltage: | 230V |
| Input Frequency: | 50/60 Hz +/- 5 Hz (auto sensing) |
| Input Connections: | - British BS1363A
- IEC-320 C20
- Schuko CEE 7/EU1-16P
|
| Cord Length: | 2.44 meters |
| Input voltage range for main operations: | 160 - 280V |
| Input voltage adjustable range for mains operation: | 100 - 280V |
| Other Input Voltages: | 220, 240 |
| Battery Type: | Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof |
| Included Battery Modules: | 2 |
| Typical recharge time: | 2.50 hour(s) |
| Replacement battery cartridge: | RBC44 |
| RBC Quantity: | 1 |
| Typical Backup Time at Half Load: | 33.9 minutes (1050 Watts) |
| Typical Backup Time at Full Load: | 14.1 minutes (2100 Watts) |
| Interface Port(s): | DB-25 RS-232, Smart-Slot |
| Available SmartSlot Interface Quantity: | 1 |
| Control panel: | LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : Overload and Bypass Indicators |
| Audible Alarm: | Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm |
| Emergency Power Off (EPO): | Yes |
| Surge energy rating: | 480 Joules |
| Filtering: | Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449 |
| Dimensions (H x W x D): | 432 x 130 x 660 mm |
| Weight: | 54.55 kg |